Faq - LOGICM
1 ) External safety devices not activating. - Incorrect connections between the photocells and the control panel.
1.1) Connect NC safety devices together in series and remove any bridges on the control panel terminal board.
2 ) Automation opens but does not close. - The automatic closing does not work.
2.1) Check that contact 1-2 is closed.
3 ) Automation opens but does not close. - Safety contacts not correctly connected or self-controlled safety edge SOFA1-SOFA2 not functioning correctly. (SA led flashing).
3.1) Check connections to terminals 6-7-8 on control panel and connections to the self-controlled safety edge SOFA1-SOFA2.
4 ) Automation opens but does not close. - Safety contacts are open. (SA led on).
4.1) Check that the safety contacts are closed correctly (N.C.).
5 ) Automation opens but does not close. - Photocells activated. (SA led on).
5.1) Check that the photocells are clean and operating correctly.
6 ) Automation does not open or close. - The motor thermal overload switch is open.
6.1) Check for continuity between the phases of the motors disconnected from the control panel.
7 ) Automation does not open or close. - Short circuited accessories. (POWER led off).
7.1) Disconnect all accessories from terminals 0-1 (voltage must be 24 V=) and reconnect one at a time.
8 ) Automation does not open or close. - Safety contacts not correctly connected or self-controlled safety edge SOFA1-SOFA2 not functioning correctly. (SA led flashing).
8.1) Check connections to terminals 6-7-8 on control panel and connections to the self-controlled safety edge SOFA1-SOFA2.
9 ) Automation does not open or close. - Safety contacts are open. (SA led on).
9.1) Check that the safety contacts are closed correctly (N.C.).
10 ) Automation does not open or close. - Release microswitch open (if installed).
10.1) Check that the hatch is closed correctly and the microswitch makes contact.
11 ) Automation does not open or close. - No power. (POWER led off).
11.1) Check that the control panel is powered correctly.
12 ) Automation does not open or close. - Blown line fuse. (POWER led off).
12.1) Replace fuse.